ICAR AIEEA-PG: Dairy Science (group 16) and Dairy Technology (group 17) is a postgraduate admission exam run by NTA for ICAR, for candidates in India. Computer-based, 2 hours, 120 multiple-choice questions, +4 for a correct answer and −1 for a wrong one (2026 bulletin). One paper per major subject group.

Source: icar.org.in.

Checked against the exam body's published information. Formats and fees change; confirm the current edition there before you book.

Instrumentation, Process Control & Automation in ICAR AIEEA-PG

Measuring and controlling temperature, flow, pressure and level in a milk plant, from sensors to PLC and SCADA.

Our 17 ICAR AIEEA-PG questions in this subject: 16 easy, 1 medium, 0 hard, across 9 units.

10 practice questions, worked

Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.

These 10 were written to ICAR AIEEA-PG and are not shown on any other exam's page.

Question 1 · easy

A thermometer gives readings that agree closely with each other but are all 0.6 °C above the reference. The instrument is:

  1. Precise but not accurate
  2. Accurate and precise once averaged
  3. Neither precise nor repeatable
  4. Accurate but not precise
Answer and working

A. Precise but not accurate

Close agreement between readings is precision (repeatability); a constant offset from the true value is a lack of accuracy, which calibration corrects. Averaging does not remove a systematic bias.

Question 2 · easy

The change of an instrument's output per unit change of its input is called its:

  1. Resolution
  2. Hysteresis
  3. Sensitivity
  4. Dead band
Answer and working

C. Sensitivity

Sensitivity is output change per unit input, such as millivolts per degree. Resolution is the smallest detectable change, hysteresis the rising–falling difference, and dead band the input range giving no output change.

Question 3 · easy

Which is a systematic rather than a random error?

  1. Readings that vary slightly when an operator reads a dial twice
  2. Fluctuations from turbulence at the point of measurement
  3. Small scatter of readings caused by electrical noise on a cable
  4. A thermometer pocket too short, so the sensor always reads low
Answer and working

D. A thermometer pocket too short, so the sensor always reads low

A short pocket causes stem conduction and a consistent low reading, a systematic error that installation or calibration must correct. Noise, reading scatter and turbulence give random variation that averaging reduces.

Question 4 · easy

Why is a three-wire connection used for an RTD read in a bridge?

  1. Lead resistances sit in adjacent bridge arms and so cancel
  2. The third wire doubles the RTD's resistance change per degree
  3. The third wire supplies cold-junction compensation for the RTD
  4. The third wire carries the recorder signal to the chart
Answer and working

A. Lead resistances sit in adjacent bridge arms and so cancel

In a three-wire bridge, one lead sits in each adjacent arm, so lead resistance and its temperature changes largely cancel. RTDs need no cold-junction compensation, and the third wire neither doubles sensitivity nor carries a chart signal.

Question 5 · easy

What does the designation Pt100 mean?

  1. A platinum element of 100 Ω at 0 °C
  2. A platinum element with 100 µV/°C output
  3. A thermocouple usable up to 100 °C
  4. A platinum element of 100 Ω at 100 °C
Answer and working

A. A platinum element of 100 Ω at 0 °C

Pt100 is a platinum RTD with 100 Ω at 0 °C; at 100 °C it reads about 138.5 Ω. It is a resistance device, not a thermocouple, and has no emf output.

Question 6 · medium

In the regenerator of an HTST pasteuriser, why is pasteurised milk kept at a higher pressure than raw milk?

  1. So that the recording thermometer reads more accurately at the outlet
  2. So that the raw milk boils off dissolved air before it reaches the heater
  3. So that any plate leak lets pasteurised milk into raw milk, not the reverse
  4. So that the timing pump needs less power to move milk through the tube
Answer and working

C. So that any plate leak lets pasteurised milk into raw milk, not the reverse

If a pinhole develops, flow goes from high to low pressure; keeping the pasteurised side higher means safe milk leaks into raw milk, which is then pasteurised. The differential has nothing to do with deaeration, pump power or recorder accuracy.

Question 7 · easy

A pneumatic valve that is spring-closed and opens when air is applied fails in which position?

  1. At its last position
  2. Open
  3. Closed
  4. Mid-position
Answer and working

C. Closed

Air-to-open valves are held shut by the spring, so on loss of air they close. Air-to-close valves fail open; ordinary spring-return valves do not hold mid or last position.

Question 8 · easy

A PLC analogue input on a 4–20 mA loop reads 0.2 mA. This most likely means:

  1. The process is above its top range value
  2. A broken wire or failed transmitter
  3. The loop is at half scale
  4. The process is at the bottom of its range
Answer and working

B. A broken wire or failed transmitter

A live zero of 4 mA means any reading well below it signals a fault such as an open circuit. The bottom of the range is 4 mA, not near zero.

Question 9 · easy

If the SCADA computer in a dairy fails, what normally happens to the process?

  1. The flow diversion valve locks in forward flow until the SCADA link returns
  2. All PLCs stop and every valve goes to its fail-safe position at once
  3. The PLCs switch to manual mode and wait for an operator
  4. PLCs keep controlling; operators lose screens, alarms and data logging
Answer and working

D. PLCs keep controlling; operators lose screens, alarms and data logging

SCADA supervises; control runs in the PLCs, which carry on. Loss of SCADA removes visibility and records, which is a serious problem, but it does not by itself stop control.

Question 10 · easy

On an HTST pasteuriser, the flow diversion valve sends milk forward only when:

  1. The homogeniser pressure has reached its set point
  2. The holding-tube outlet temperature is at or above the legal cut-in value
  3. The balance tank is full and the raw-milk pump is running
  4. The cooling section outlet is below the storage temperature
Answer and working

B. The holding-tube outlet temperature is at or above the legal cut-in value

The recorder-controller at the holding-tube outlet decides forward flow; below the cut-out it diverts. Balance-tank level, cooling and homogeniser pressure are not the forward-flow condition.

A study plan for Instrumentation, Process Control & Automation in ICAR AIEEA-PG

This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.

  1. First, the heavy units (59% of the 17 questions): Generalised measurement system and instrument characteristics (4, 24%); Control modes: on-off, P, PI and PID (3, 18%); Temperature measurement: thermocouples, RTDs and recorders (3, 18%).

    Read the manual chapters for these first and do every worked question you can find on them.

  2. Then the middle band: Pressure, flow and level measurement (2, 12%); Automation of pasteurisers, CIP and milk reception (1, 6%); Final control elements: valves and drives (1, 6%).

    Aim for one sitting per unit, then mixed questions across them.

  3. Then the lighter units: pH, conductivity and inline composition sensors (1, 6%); Programmable logic controllers (1, 6%); SCADA and distributed control systems (1, 6%).

    Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.

  4. Bank the easy marks: Generalised measurement system and instrument characteristics (4 easy of 4); Control modes: on-off, P, PI and PID (3 easy of 3).

    Do these early in revision so they are fast on the day.

  5. Finish timed. Sit the subject as a timed set without notes, mark it, and send each wrong answer back to its unit above.

Last updated · How Laisha writes and checks its pages · Report a mistake

Ask Laisha about this

Opens Laisha's chat with your question ready to send. Sign in or start free.

Unlock every question — ICAR AIEEA-PG Instrumentation, Process Control & Automation

US$10 a month · one price worldwide · cancel any time

  • Every practice question in this subject, with full working
  • Timed exam papers and progress by unit
  • Ask Laisha to explain any answer — up to 1,000 questions a month
Free or Smarter
FreeSmarter
Grow guides, pest pages, articlesRead allRead all
Ask Laisha5 a dayUp to 1,000 a month
Exam practiceThe sample on each pageEvery question, timed papers
Crop calendar and pest alerts—For your own fields
Calculators and tools—All
Uploads and reports—100 a month, real files
10 days free for every new account, no card.