NCEES PE Agricultural and Biological Engineering · USA · NCEES (ASABE is the content partner)
Original practice questions written to the published syllabus · not past papersNCEES PE Agricultural and Biological Engineering is a licensing and registration exam run by NCEES (ASABE is the content partner), for candidates in USA. Computer-based, 85 questions, 9.5-hour appointment (8.5 hours of exam). Once a year (next: 28 Oct 2026). Closed book with the electronic NCEES handbook and supplied searchable ASABE standards; SI and US customary units.
Source: ncees.org.
Checked against the exam body's published information. Formats and fees change; confirm the current edition there before you book.
Applying sensors and data acquisition in system problems: flow measurement for irrigation and processing, environmental monitoring of animal and plant facilities, control strategies for dryers and ventilation.
Measuring temperature, pressure, flow, force and moisture, logging the data, and controlling processes automatically.
Our 45 NCEES PE Agricultural and Biological Engineering questions in this subject: 6 easy, 22 medium, 17 hard, across 11 units.
Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.
These 10 were written to NCEES PE Agricultural and Biological Engineering and are not shown on any other exam's page.
PTO power is calculated as P = 2πNT/60. Torque T is measured to ±1.0% and shaft speed N to ±0.5%, independently. What is the most probable relative uncertainty in P?
D. ±1.12%
For a product of powers, relative uncertainties combine by root sum of squares (each exponent is 1): √(1.0² + 0.5²) = 1.12%. ±1.50% is the worst-case arithmetic sum; ±0.75% is the average; ±0.50% keeps only the smaller term.
Dryer plenum air warms steadily at 2 °C per minute. The air-temperature sensor is first-order with a time constant of 30 s. Once the ramp is established, how far does the reading lag behind the true temperature?
B. 1.0 °C
For a ramp, a first-order sensor lags by rate × τ = (2 °C/60 s) × 30 s = 1.0 °C. 60 °C multiplies 2 by 30 without converting minutes to seconds; 2.0 °C would correspond to a 60 s time constant; 0.033 °C is the rate per second, not the lag.
An infrared thermometer set to emissivity 0.95 is pointed at the bare polished stainless-steel outer wall of a hot-air duct and reads far below a contact thermocouple. What is the most likely cause?
A. The polished metal has low emissivity, so it emits less than the 0.95 setting assumes
Shiny metals have low emissivity (often well below 0.3), so with the instrument set to 0.95 it underestimates temperature, and it also picks up reflected radiation from the surroundings. The fix is high-emissivity tape or paint on the spot, or a contact measurement. Infrared does not see through steel.
A turbine meter on a fertigation line has a K-factor of 50 pulses per litre. A counter records 1500 pulses in 60 s. What is the flow rate?
A. 30 L/min
Volume = 1500/50 = 30 L in 60 s, i.e. 30 L/min (0.5 L/s). 75 L/min multiplies 1500 by 50 and divides by 1000; 3000 L/min multiplies the K-factor by the 60 s count period; 1.25 L/min takes the 75 L/min slip and divides it by 60 again.
A TDR probe has 0.20 m rods. The two-way travel time of the pulse along the rods is 5.33 ns (c = 3×10⁸ m/s). Using the Topp equation, what is the volumetric water content?
B. 0.291 m³/m³
Ka = (c·t/2L)² = (3×10⁸ × 5.33×10⁻⁹ / 0.40)² = (3.998)² = 16.0. Topp: θv = −0.053 + 0.0292(16) − 5.5×10⁻⁴(256) + 4.3×10⁻⁶(4096) = 0.291. 0.467 keeps only the linear term; 0.689 treats 5.33 ns as a one-way time (Ka = 64); 0.055 forgets to square, using Ka = 4.
Greenhouse air is at 25 °C and 70% relative humidity. Using es = 0.6108 exp(17.27T/(T+237.3)) kPa, what is the vapour pressure deficit?
A. 0.95 kPa
es(25 °C) = 0.6108 × exp(17.27 × 25/262.3) = 3.168 kPa; ea = 0.70 × 3.168 = 2.217 kPa; VPD = es − ea = 0.95 kPa. 2.22 kPa is the actual vapour pressure, 3.17 kPa the saturation value, and 0.30 is the RH deficit fraction without units of pressure.
In a grain plant, the bucket elevator motor trips on overload while the intake conveyor and the bin-fill conveyor are running. What should the interlock logic do?
B. Stop the intake conveyor feeding the elevator at once, and let the bin-fill conveyor run on to empty
Every machine feeding a stopped machine must stop, or grain piles up and chokes the elevator. Machines downstream can run on to empty. Automatic restart after an overload trip is unsafe; the cause must be found first.
In an ultimate-cycle test on a dryer burner loop, sustained oscillation occurs at Ku = 8 with period Pu = 120 s. What are the Ziegler–Nichols PID settings?
D. Kp = 4.8, Ti = 60 s, Td = 15 s
Ziegler–Nichols PID: Kp = 0.6Ku = 4.8, Ti = Pu/2 = 60 s, Td = Pu/8 = 15 s. Kp = 3.6 with Ti = 100 s is the PI rule; 0.5Ku is the P-only rule. These settings give quarter-amplitude decay and are usually softened in practice.
What is the main trade-off of a mesh topology compared with a star topology in a field sensor network?
B. It extends coverage around obstacles, but relaying nodes use more energy and add latency
In a mesh, nodes relay each other's packets, so the network can reach around obstacles and beyond one hop, at the cost of extra listening and transmitting energy on relaying nodes, and more complex routing. A star needs every node in direct range of the gateway.
An automated irrigation system starts a pump whenever one soil-moisture node reports a value below threshold. One night the node's probe is pulled partly out of the soil by a rodent and the pump runs for 10 hours. What design change best prevents this?
D. Cross-check against other sensors or a water-balance model, flag sudden steps, and cap run time
No sensor is immune to physical failure. Automated decisions should check plausibility (sudden steps, out-of-range values), agree with redundant sensors or a model, and have hard limits such as maximum run time and flow-meter confirmation. More frequent faulty readings do not help.
This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.
Read the manual chapters for these first and do every worked question you can find on them.
Aim for one sitting per unit, then mixed questions across them.
Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.
Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.
Do these early in revision so they are fast on the day.
Last updated · How Laisha writes and checks its pages · Report a mistake
US$10 a month · one price worldwide · cancel any time
| Free | Smarter | |
|---|---|---|
| Grow guides, pest pages, articles | Read all | Read all |
| Ask Laisha | 5 a day | Up to 1,000 a month |
| Exam practice | The sample on each page | Every question, timed papers |
| Crop calendar and pest alerts | — | For your own fields |
| Calculators and tools | — | All |
| Uploads and reports | — | 100 a month, real files |
An AI operating system for agriculture: free guides, manuals and tools written for every country.