Original practice questions written to the published syllabus · not past papersGATE — Agricultural Engineering (AG) is a postgraduate admission exam run by IITs and IISc on rotation (2027: IIT Madras), for candidates in India. Computer-based, 3 hours, 100 marks (15 General Aptitude + 85 technical: 25 one-mark and 30 two-mark questions). MCQ, MSQ and NAT; negative marking on MCQ only (−1/3 for one-mark, −2/3 for two-mark); no partial credit on MSQ. On-screen virtual calculator.
Source: gate2027.iitm.ac.in.
Checked against the exam body's published information. Formats and fees change; confirm the current edition there before you book.
Refrigeration sits in the Dairy and Food Engineering and Storage Systems parts of the syllabus. Expect one- or two-mark numerical-answer questions: COP from given enthalpies or from Carnot temperatures, tonnes of refrigeration, mass flow and compressor power; conduction through a composite cold-store wall (the most repeated calculation); product and latent heat loads; freezing time by Plank's equation; and psychrometric properties feeding a load. Read units carefully: kJ/min against kW and °C against K are the usual traps.
Refrigeration cycles, equipment and cold-store design, from COP to the heat load of a room full of potatoes.
Our 40 GATE questions in this subject: 9 easy, 19 medium, 12 hard, across 14 units.
Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.
These 10 were written to GATE and are not shown on any other exam's page.
A reversed Carnot refrigerator works between an evaporator at -10 °C and a condenser at 40 °C. Its COP is closest to
D. 5.26
COP = T_L/(T_H − T_L) = 263.15/(40 − (-10)) = 263.15/50 = 5.26. 6.26 is the heat-pump COP (T_H/ΔT); 0.20 is the size of −10/50, from using Celsius temperatures; 0.80 uses T_H/ΔT with T_H in Celsius, mixing the heat-pump form with the wrong temperature scale.
A two-stage ammonia system has suction pressure 2.0 bar and condensing pressure 12.5 bar. Using the usual first choice for intermediate pressure, the intercooler pressure is about
D. 5.0 bar
The geometric mean √(p_s p_d) = √(2.0 × 12.5) = 5.0 bar roughly equalises the pressure ratios (2.5 each) and the work of the stages. The arithmetic mean 7.25 bar gives unequal ratios; 6.25 is the overall pressure ratio, not a pressure, and 10.5 bar is the pressure difference.
One tonne of refrigeration (TR) is equal to about
C. 3.517 kW
1 TR = 12,000 Btu/h = 211 kJ/min ≈ 3.517 kW. 12 kW confuses it with 12,000 Btu/h; 4.187 is the specific heat of water in kJ/kg K.
From a p–h chart an ammonia cycle has h1 = 1420 kJ/kg (suction), h2 = 1650 kJ/kg (discharge) and h3 = 320 kJ/kg (condenser outlet). For a capacity of 50 kW, the refrigerant mass flow rate is
A. 0.0455 kg/s
Refrigerating effect = h1 − h4 = 1420 − 320 = 1100 kJ/kg (h4 = h3). m = 50/1100 = 0.0455 kg/s. Using the condenser enthalpy change (1330) or the work (230) as divisor are the usual slips (0.0376 and 0.2174 kg/s); dividing by the suction enthalpy alone gives 0.0352 kg/s. COP here = 1100/230 = 4.78.
Water enters a cooling tower at 35 °C and leaves at 30 °C when the ambient wet-bulb temperature is 26 °C. The approach and range are
C. Approach 4 K, range 5 K
Range = inlet − outlet water = 35 − 30 = 5 K. Approach = outlet water − wet bulb = 30 − 26 = 4 K. Swapping the two definitions is the usual error.
A water-cooled condenser rejects 50 kW with refrigerant condensing at 40 °C. Water enters at 30 °C and leaves at 35 °C. With U = 800 W/m² K, the required area is about
B. 8.66 m²
ΔT1 = 10 K, ΔT2 = 5 K. LMTD = (10 − 5)/ln(10/5) = 7.21 K. A = Q/(U·LMTD) = 50,000/(800 × 7.21) = 8.66 m². The arithmetic mean (7.5 K) gives 8.33 m²; using the water rise (5 K) gives 12.5 m²; 0.0087 m² forgets kW → W.
A thermostatic expansion valve is designed to maintain a nearly constant
B. Superheat of vapour at the evaporator outlet
The bulb on the suction line senses outlet temperature, and the diaphragm balances bulb pressure against evaporator pressure plus spring: the controlled variable is superheat. Constant evaporator pressure is the automatic (constant-pressure) valve; liquid level is a float valve.
Using h = 1.005t + ω(2501 + 1.88t), the enthalpy of air at 30 °C and humidity ratio 0.015 kg/kg is about
A. 68.5 kJ/kg dry air
h = 1.005×30 + 0.015×(2501 + 56.4) = 30.15 + 38.36 = 68.5 kJ/kg. 30.1 (30.15) is dry air only; 67.7 omits the vapour sensible term, and 31.0 omits the latent heat, which is the largest part of the vapour term.
A cold-store wall is 230 mm brick (k = 0.7), 100 mm polyurethane (k = 0.025) and 15 mm plaster (k = 0.7 W/m K). Outside and inside film coefficients are 23 and 8 W/m² K. For 100 m² of wall and a 35 K temperature difference, the heat gain is about
A. 775 W
R = 1/23 + 0.23/0.7 + 0.10/0.025 + 0.015/0.7 + 1/8 = 0.0435 + 0.3286 + 4.000 + 0.0214 + 0.125 = 4.518 m² K/W; U = 0.2213 W/m² K. Q = 0.2213 × 100 × 35 = 775 W. Ignoring films gives 805 W; insulation alone gives 875 W; multiplying by R instead of dividing gives a huge wrong number. 15815 W multiplies by R (4.518 × 100 × 35).
100 t of potatoes (c_p = 3.6 kJ/kg K) enter a store at 30 °C and must be cooled to 4 °C in 24 h. The average product cooling load is about
C. 30.8 TR
Q = m c_p Δt = 100,000 × 3.6 × 26 = 9,360,000 kJ. ÷ 86,400 s = 108.3 kW = 30.8 TR. 108.3 is the kW value mislabelled; using 30 K instead of 26 K gives 35.5 TR; dividing by 3,600 treats the day as one hour. 739 TR divides by 3,600 instead of 86,400 (2,600 kW/3.517).
This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.
Read the manual chapters for these first and do every worked question you can find on them.
Aim for one sitting per unit, then mixed questions across them.
Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.
Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.
Do these early in revision so they are fast on the day.
Last updated · How Laisha writes and checks its pages · Report a mistake
US$10 a month · one price worldwide · cancel any time
| Free | Smarter | |
|---|---|---|
| Grow guides, pest pages, articles | Read all | Read all |
| Ask Laisha | 5 a day | Up to 1,000 a month |
| Exam practice | The sample on each page | Every question, timed papers |
| Crop calendar and pest alerts | — | For your own fields |
| Calculators and tools | — | All |
| Uploads and reports | — | 100 a month, real files |
An AI operating system for agriculture: free guides, manuals and tools written for every country.