LAISHA
Open Laisha

ASRB NET Refrigeration, Air-Conditioning & Cold-Chain Engineering: practice questions

ASRB NET — Farm Machinery & Power / Land & Water Management Engineering / Agricultural Structures & Process Engineering · India · Agricultural Scientists Recruitment Board (ICAR)

Original practice questions written to the published syllabus · not past papers
10worked here, free
63written to this exam in this subject
14syllabus units

About ASRB NET

ASRB NET — Farm Machinery & Power / Land & Water Management Engineering / Agricultural Structures & Process Engineering is a specialist certification exam run by Agricultural Scientists Recruitment Board (ICAR), for candidates in India. NET: 150 MCQs, 150 marks, 2 hours, −1/3 per wrong answer, English/Hindi, PG level. Combined NET/ARS/SMS/STO recruitment runs prelims, mains and interview.

Official site: pw.live.

We have not been able to confirm these details against the exam body's own specification, so fees, dates and pass marks are left out on purpose. Check the current format, eligibility, fees and dates on the official site.

Refrigeration, Air-Conditioning & Cold-Chain Engineering in ASRB NET

Conceptual MCQs across the whole subject with an emphasis on cold-storage design, insulation materials, controlled atmosphere and pre-cooling, and standard numerical relations.

Refrigeration cycles, equipment and cold-store design, from COP to the heat load of a room full of potatoes.

Our 63 ASRB NET questions in this subject: 20 easy, 33 medium, 10 hard, across 14 units.

10 practice questions, worked

Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.

These 10 were written to ASRB NET and are not shown on any other exam's page.

Question 1 · hard

An operator of a lithium bromide chiller finds that the solution flow has stopped after cooling water became unusually cold at low load. The most likely cause is

  1. Freezing of the ammonia refrigerant in the evaporator caused by the very low load
  2. Oil logging of the generator
  3. Loss of hydrogen charge
  4. Crystallisation of strong solution, especially in the solution heat exchanger
Answer and working

D. Crystallisation of strong solution, especially in the solution heat exchanger

Strong LiBr solution crystallises if it becomes too concentrated or too cold; very cold absorber water and low load are classic triggers, and the solution heat exchanger is the usual site. The machine contains no ammonia, hydrogen or compressor oil.

Question 2 · medium

By the standard numbering rule for halocarbons, chlorodifluoromethane (CHClF2) is designated

  1. R-21
  2. R-122
  3. R-12
  4. R-22
Answer and working

D. R-22

R-XYZ: X = C − 1 = 0 (dropped), Y = H + 1 = 2, Z = F = 2, giving R-22. R-12 is CCl2F2 (no hydrogen). R-21 would have only one fluorine. R-122 forgets to subtract 1 from the carbon count (X = C = 1).

Question 3 · easy

Ozone depletion potential (ODP) is expressed relative to

  1. R-11, taken as 1.0
  2. Carbon dioxide, taken as 1.0
  3. Ammonia, taken as 1.0
  4. R-134a, taken as 1.0
Answer and working

A. R-11, taken as 1.0

ODP compares ozone destruction with that of trichlorofluoromethane, R-11. Carbon dioxide is the reference for global warming potential, not ODP; R-134a and ammonia have ODP zero.

Question 4 · medium

Refrigerant blends in the R-400 series differ from pure refrigerants in that they

  1. Show a temperature glide during phase change at constant pressure
  2. Have zero GWP
  3. Are always azeotropic
  4. Cannot be used with thermostatic expansion valves because of their composition
Answer and working

A. Show a temperature glide during phase change at constant pressure

R-400 blends are zeotropic: the composition of vapour and liquid differs, so saturation temperature changes along the evaporator and condenser. Azeotropic blends are the R-500 series.

Question 5 · hard

On the p–h chart of a zeotropic blend such as R-407C, the isotherms inside the two-phase dome

  1. Do not exist, because zeotropic blends pass straight from liquid to vapour with no two-phase region
  2. Are vertical, like isenthalps
  3. Are horizontal, as for a pure refrigerant
  4. Slope, because saturation temperature changes during phase change at constant pressure
Answer and working

D. Slope, because saturation temperature changes during phase change at constant pressure

The temperature glide of zeotropic blends means that at constant pressure the bubble and dew temperatures differ, so isotherms inside the dome are inclined. For pure refrigerants and azeotropes they are horizontal.

Question 6 · medium

When the load on an evaporator fed by an automatic (constant-pressure) expansion valve increases, the valve tends to

  1. Close, starving the evaporator just when more refrigerant is needed
  2. Keep the liquid level constant
  3. Hold superheat constant
  4. Open wide and flood the evaporator
Answer and working

A. Close, starving the evaporator just when more refrigerant is needed

Higher load tends to raise evaporator pressure; the valve acts to hold pressure constant, so it throttles down. That inverse response is why it is used only for small, steady loads.

Question 7 · medium

A room has a sensible heat gain of 30 kW and a latent heat gain of 10 kW. The room sensible heat factor is

  1. 0.75
  2. 3.00
  3. 0.33
  4. 0.25
Answer and working

A. 0.75

SHF = sensible/(sensible + latent) = 30/40 = 0.75. 3 is the sensible-to-latent ratio, not the SHF. 0.33 is latent/sensible (10/30), and 0.25 is latent/total (10/40).

Question 8 · medium

Freezer rooms built on the ground are given underfloor heating or a ventilated void because

  1. It raises the humidity of the room
  2. It reduces the transmission heat load through the floor into the freezer room
  3. It prevents condensation on the ceiling
  4. Otherwise the ground beneath freezes, ice lenses form and the floor heaves
Answer and working

D. Otherwise the ground beneath freezes, ice lenses form and the floor heaves

Heat drawn from the soil over months lowers it below 0 °C; water migrating to the freezing front forms ice lenses that lift and crack the slab. The heating adds slightly to the load; it does not reduce it.

Question 9 · medium

Extruded polystyrene is often preferred to expanded polystyrene beneath cold-store floor slabs mainly for its

  1. Higher compressive strength and lower water absorption
  2. Higher vapour permeability
  3. Non-combustibility
  4. Lower cost per cubic metre
Answer and working

A. Higher compressive strength and lower water absorption

Under-slab insulation carries floor and racking loads and may be exposed to ground moisture; extruded polystyrene's closed-cell structure gives strength and low water uptake. It is combustible, and low vapour permeability, not high, is its merit.

Question 10 · medium

Vacuum cooling is best suited to

  1. Potatoes in bulk
  2. Leafy vegetables such as lettuce, which have a high surface-to-mass ratio
  3. Whole melons
  4. Frozen meat cartons, which need rapid removal of their remaining heat before long-term storage
Answer and working

B. Leafy vegetables such as lettuce, which have a high surface-to-mass ratio

Vacuum cooling works by evaporating water from the product surface at low pressure, so it is fastest for products with large surface per unit mass. Dense, thick-skinned produce cools slowly. It removes about 1% of weight for each 5–6 K of cooling.

A study plan for Refrigeration, Air-Conditioning & Cold-Chain Engineering in ASRB NET

This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.

  1. First, the heavy units (48% of the 63 questions): Refrigerated transport and cold-chain logistics (8, 13%); Refrigerants: ODP and GWP (7, 11%); Compressors (5, 8%); Expansion devices (5, 8%); Ice-bank systems (5, 8%).

    Read the manual chapters for these first and do every worked question you can find on them.

  2. Then the middle band: Insulation and vapour barriers (5, 8%); Vapour-absorption refrigeration (5, 8%); Cold-store heat load: infiltration, occupancy and equipment (4, 6%); Cold-store heat load: transmission, product and respiration (4, 6%); Condensers and evaporators (4, 6%).

    Aim for one sitting per unit, then mixed questions across them.

  3. Then the lighter units: Psychrometric air-conditioning processes (4, 6%); Pressure-enthalpy charts (3, 5%); Vapour-compression refrigeration cycle (3, 5%); COP and tonnes of refrigeration (1, 2%).

    Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.

  4. Leave time for the hard ones: Pressure-enthalpy charts (1 hard of 3), Cold-store heat load: infiltration, occupancy and equipment (1 hard of 4), Cold-store heat load: transmission, product and respiration (1 hard of 4).

    Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.

  5. Bank the easy marks: COP and tonnes of refrigeration (1 easy of 1); Vapour-compression refrigeration cycle (2 easy of 3).

    Do these early in revision so they are fast on the day.

  6. Finish timed. Sit the subject as a timed set without notes, mark it, and send each wrong answer back to its unit above.

Last updated · How Laisha writes and checks its pages · Report a mistake

Ask Laisha about this

Opens Laisha's chat with your question ready to send. Sign in or start free.

Unlock every question — ASRB NET Refrigeration, Air-Conditioning & Cold-Chain Engineering

US$10 a month · one price worldwide · cancel any time

  • Every practice question in this subject, with full working
  • Timed exam papers and progress by unit
  • Ask Laisha to explain any answer — up to 1,000 questions a month
Free or Smarter
FreeSmarter
Grow guides, pest pages, articlesRead allRead all
Ask Laisha5 a dayUp to 1,000 a month
Exam practiceThe sample on each pageEvery question, timed papers
Crop calendar and pest alerts—For your own fields
Calculators and tools—All
Uploads and reports—100 a month, real files
10 days free for every new account, no card.