ICAR AIEEA-PG Refrigeration, Air-Conditioning & Cold-Chain Engineering: practice questions

ICAR AIEEA-PG — Agricultural Engineering & Technology (Major Subject Group 10) · India · National Testing Agency for ICAR

Original practice questions written to the published syllabus · not past papers
10worked here, free
68written to this exam in this subject
14syllabus units

About ICAR AIEEA-PG

ICAR AIEEA-PG — Agricultural Engineering & Technology (Major Subject Group 10) is a postgraduate admission exam run by National Testing Agency for ICAR, for candidates in India. Computer-based, 120 minutes, 120 MCQs, +4 / −1, English only (2026 bulletin). One paper for the whole subject group.

Source: icar.org.in.

Checked against the exam body's published information. Formats and fees change; confirm the current edition there before you book.

Refrigeration, Air-Conditioning & Cold-Chain Engineering in ICAR AIEEA-PG

Unit VI asks single-answer MCQs on refrigeration and air-conditioning, cold stores and heating and cooling load calculation: the four processes of the cycle, TR definition, refrigerant designation and ODP/GWP, absorption pairs, expansion devices, psychrometric processes, cold-store load components, insulation and vapour-barrier placement. Negative marking rewards precise definitions.

Refrigeration cycles, equipment and cold-store design, from COP to the heat load of a room full of potatoes.

Our 68 ICAR AIEEA-PG questions in this subject: 31 easy, 35 medium, 2 hard, across 14 units.

10 practice questions, worked

Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.

These 10 were written to ICAR AIEEA-PG and are not shown on any other exam's page.

Question 1 · medium

Subcooling the liquid refrigerant leaving the condenser, with evaporating and condensing pressures unchanged, will

  1. Reduce the refrigerating effect because h4 rises when the liquid is cooled further
  2. Increase the refrigerating effect per kg without increasing compressor work per kg
  3. Increase compressor work per kg and lower COP, because the colder liquid needs more pumping
  4. Have no effect because throttling is isenthalpic
Answer and working

B. Increase the refrigerating effect per kg without increasing compressor work per kg

Subcooling lowers h3, and since h4 = h3 the refrigerating effect h1 − h4 grows. Suction state 1 is unchanged, so the work h2 − h1 is unchanged and COP rises. Throttling being isenthalpic is exactly why the lower h3 carries through to h4.

Question 2 · medium

In the three-fluid (diffusion) absorption refrigerator, hydrogen is used to

  1. Act as the refrigerant, evaporating in the evaporator to absorb heat from the cabinet
  2. Equalise total pressure throughout the circuit so that no solution pump is needed
  3. Absorb ammonia in the absorber
  4. Cool the generator
Answer and working

B. Equalise total pressure throughout the circuit so that no solution pump is needed

Hydrogen fills the evaporator and absorber so that ammonia evaporates at a low partial pressure while total pressure is uniform; circulation is by a heat-driven bubble pump and gravity. Water, not hydrogen, is the absorbent, and ammonia is the refrigerant.

Question 3 · medium

At the evaporator pressure, saturated liquid enthalpy is 180 kJ/kg and saturated vapour enthalpy 390 kJ/kg. Liquid at 250 kJ/kg is throttled into the evaporator. The dryness fraction at evaporator inlet is

  1. 0.641
  2. 0.333
  3. 0.359
  4. 0.667
Answer and working

B. 0.333

x = (h4 − h_f)/(h_g − h_f) = (250 − 180)/(390 − 180) = 70/210 = 0.333. 0.667 is the liquid fraction; h4/h_g ignores the liquid enthalpy datum. 0.641 is h4/h_g (250/390), and 0.359 is (h_g − h4)/h_g (140/390).

Question 4 · medium

As the evaporating temperature of a reciprocating compressor falls with condensing temperature fixed, its volumetric efficiency

  1. Rises, because suction gas is denser
  2. Falls, as a higher pressure ratio makes clearance gas re-expand over more stroke
  3. Is unchanged, because swept volume is fixed
  4. Rises, because discharge temperature falls and the valves open earlier in each stroke
Answer and working

B. Falls, as a higher pressure ratio makes clearance gas re-expand over more stroke

η_v = 1 + C − C(p_d/p_s)^(1/n) falls as p_d/p_s rises. Suction gas actually becomes less dense at lower evaporating temperature, which also reduces mass flow.

Question 5 · medium

A practical advantage of the capillary tube is that it allows a low-starting-torque compressor motor because

  1. High- and low-side pressures equalise through it while the compressor is off
  2. It adjusts its bore to the load
  3. It stores a large reserve of liquid refrigerant that it releases to the compressor on start-up
  4. It prevents flash gas at the evaporator inlet
Answer and working

A. High- and low-side pressures equalise through it while the compressor is off

With no valve to close, pressures balance during the off cycle, so the compressor starts against no pressure difference. It has no reserve, no adjustment, and flash gas still forms.

Question 6 · easy

During sensible heating of moist air, which property remains constant?

  1. Relative humidity
  2. Wet-bulb temperature
  3. Enthalpy
  4. Humidity ratio
Answer and working

D. Humidity ratio

No moisture is added or removed, so ω stays constant and the process is horizontal on the chart. Relative humidity falls because the saturation pressure rises; wet-bulb and enthalpy rise.

Question 7 · easy

By Siebel's relation, the specific heat above freezing of a fruit with 80% water is about

  1. 2.68 kJ/kg K
  2. 1.85 kJ/kg K
  3. 3.35 kJ/kg K
  4. 3.52 kJ/kg K
Answer and working

D. 3.52 kJ/kg K

c_p = 3.35 × 0.8 + 0.84 = 3.52 kJ/kg K. 1.85 is the below-freezing relation; omitting the 0.84 solids term gives 2.68.

Question 8 · easy

In a cold-store wall, the vapour barrier should be placed

  1. On the cold (inner) side of the insulation
  2. In the middle of the insulation
  3. On both faces, with the inner one sealed more tightly
  4. On the warm (outer) side of the insulation
Answer and working

D. On the warm (outer) side of the insulation

Vapour moves from warm to cold. A barrier on the warm side stops it before it reaches layers cold enough to condense or freeze it. A tight barrier on the cold side traps any moisture that enters.

Question 9 · medium

Milk cooled by chilled water from an ice bank cannot freeze on the heat-exchanger surface because

  1. Milk has no freezing point
  2. The plate cooler is insulated, so the milk never reaches the temperature of the chilled water
  3. The chilled water cannot fall much below 0 °C, which is above milk's freezing point
  4. The ice bank runs only at night
Answer and working

C. The chilled water cannot fall much below 0 °C, which is above milk's freezing point

Water in contact with melting ice stays near 0 °C, and milk freezes slightly below 0 °C, so there is no risk. Direct-expansion surfaces run colder and need agitation and control to avoid freezing.

Question 10 · easy

In the cold chain, the step that removes field heat from produce immediately after harvest is called

  1. Pre-cooling
  2. Blanching
  3. Curing
  4. Controlled-atmosphere storage
Answer and working

A. Pre-cooling

Pre-cooling (forced-air, hydro, vacuum, room or ice cooling) brings produce quickly toward storage temperature. Curing heals wounds at warm temperatures; blanching is a heat treatment before freezing vegetables.

A study plan for Refrigeration, Air-Conditioning & Cold-Chain Engineering in ICAR AIEEA-PG

This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.

  1. First, the heavy units (44% of the 68 questions): Refrigerants: ODP and GWP (7, 10%); Cold-store heat load: transmission, product and respiration (6, 9%); Psychrometric air-conditioning processes (6, 9%); Refrigerated transport and cold-chain logistics (6, 9%); Cold-store heat load: infiltration, occupancy and equipment (5, 7%).

    Read the manual chapters for these first and do every worked question you can find on them.

  2. Then the middle band: Pressure-enthalpy charts (5, 7%); Vapour-compression refrigeration cycle (5, 7%); Compressors (4, 6%); Condensers and evaporators (4, 6%); COP and tonnes of refrigeration (4, 6%).

    Aim for one sitting per unit, then mixed questions across them.

  3. Then the lighter units: Expansion devices (4, 6%); Ice-bank systems (4, 6%); Insulation and vapour barriers (4, 6%); Vapour-absorption refrigeration (4, 6%).

    Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.

  4. Leave time for the hard ones: Cold-store heat load: transmission, product and respiration (2 hard of 6).

    Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.

  5. Bank the easy marks: COP and tonnes of refrigeration (3 easy of 4); Ice-bank systems (3 easy of 4).

    Do these early in revision so they are fast on the day.

  6. Finish timed. Sit the subject as a timed set without notes, mark it, and send each wrong answer back to its unit above.

Last updated · How Laisha writes and checks its pages · Report a mistake

Ask Laisha about this

Opens Laisha's chat with your question ready to send. Sign in or start free.

Unlock every question — ICAR AIEEA-PG Refrigeration, Air-Conditioning & Cold-Chain Engineering

US$10 a month · one price worldwide · cancel any time

  • Every practice question in this subject, with full working
  • Timed exam papers and progress by unit
  • Ask Laisha to explain any answer — up to 1,000 questions a month
Free or Smarter
FreeSmarter