Electrical Machines & Power Utilisation in ICAR AIEEA-PG

Quick recall and one-step numericals on electric motors and power distribution: synchronous speed and slip, rotor frequency, torque–slip relations and the effect of voltage and rotor resistance, star-delta and autotransformer starting ratios, single-phase motor types and their starting methods, DC motor EMF, back EMF and speed, transformer connections and all-day efficiency, and power-factor correction.

Motors and power supply on farms and in processing plants: choosing, starting, protecting and paying for electric drives.

Our 72 ICAR AIEEA-PG questions in this subject: 41 easy, 28 medium, 3 hard, across 10 units.

10 practice questions, worked

Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.

These 10 were written to ICAR AIEEA-PG and are not shown on any other exam's page.

Question 1 · easy

Which DC motor gives the highest starting torque per ampere and so suits traction-type loads?

  1. Separately excited motor at weak field
  2. Shunt motor running on a full field
  3. Series motor
  4. Permanent-magnet motor of equal rating
Answer and working

C. Series motor

In a series motor flux rises with armature current, so torque rises roughly as Ia² below saturation, giving the highest starting torque per ampere. Shunt, separately excited and permanent-magnet motors have nearly fixed flux, so torque rises only in proportion to current; weakening the field lowers torque per ampere further.

Question 2 · easy

What is the full-load low-voltage line current of a three-phase 63 kVA, 11 kV/433 V distribution transformer feeding an irrigation cluster?

  1. 84.0 A
  2. 3.31 A
  3. 48.5 A
  4. 145.5 A
Answer and working

A. 84.0 A

I = S/(√3 V) = 63000/(1.732 × 433) = 84.0 A. 145.5 A forgets the √3 of a three-phase supply. 3.31 A is the HV-side current. 48.5 A divides by 3 instead of √3.

Question 3 · easy

What must a three-phase motor have for it to be started with a star-delta starter?

  1. Three winding ends brought out and a star rating at line voltage
  2. A centrifugal switch that opens the starting winding at speed
  3. A wound rotor whose three phases are brought out to slip rings
  4. Six winding ends brought out and a delta rating at line voltage
Answer and working

D. Six winding ends brought out and a delta rating at line voltage

The starter connects the windings first in star and then in delta, so both ends of each phase (six terminals) must be accessible, and the motor must run in delta at the supply line voltage. Slip rings are for rotor-resistance starting; centrifugal switches belong to single-phase motors.

Question 4 · easy

At roughly what speed does the centrifugal switch of a split-phase or capacitor-start motor disconnect the starting winding?

  1. About 20–30 % of synchronous speed
  2. About 70–80 % of synchronous speed
  3. Exactly at synchronous speed
  4. About 105 % of synchronous speed
Answer and working

B. About 70–80 % of synchronous speed

The switch opens at about 70–80 % of synchronous speed, after the motor has enough running torque on the main winding. At 20–30 % the motor would lack torque; induction motors never reach or exceed synchronous speed in motoring.

Question 5 · easy

Under IEC 60034-1, what does duty type S1 mean?

  1. Continuous running at constant load until thermal equilibrium
  2. Short-time running followed by a long rest to cool completely
  3. Duty with frequent electrical braking and reversal of rotation
  4. Intermittent periodic duty with equal running and resting periods
Answer and working

A. Continuous running at constant load until thermal equilibrium

S1 is continuous duty: constant load long enough to reach thermal equilibrium, as for irrigation pumps. S2 is short-time duty, S3 intermittent periodic duty, and higher S-numbers cover starting, braking and speed changes.

Question 6 · easy

A 400 V, 50 Hz motor is fed by a VFD at 35 Hz under constant V/f control. What voltage does the drive apply?

  1. 571 V
  2. 280 V
  3. 400 V
  4. 196 V
Answer and working

B. 280 V

V/f = 400/50 = 8 V/Hz; at 35 Hz V = 8 × 35 = 280 V. Keeping 400 V would over-flux and saturate the motor. 196 V scales by (35/50)². 571 V inverts the ratio.

Question 7 · medium

A centrifugal pump working against friction only is slowed to 80 % speed. What happens to its head?

  1. Stays at 100 % of the original
  2. Falls to 80 % of the original
  3. Falls to 64 % of the original
  4. Falls to 51.2 % of the original
Answer and working

C. Falls to 64 % of the original

Head ∝ N², so 0.8² = 0.64. 80 % is the flow ratio, 51.2 % the power ratio. Head does not stay constant when speed changes.

Question 8 · medium

What is the main purpose of converting a rural low-voltage network to a high-voltage distribution system (HVDS)?

  1. Allow every farm to be supplied by single-wire earth return in place of 11 kV
  2. Replace overhead medium-voltage lines with underground low-voltage cables
  3. Shorten low-voltage lines by placing small transformers near each few consumers
  4. Raise the low-voltage supply from 230 V to 400 V for each rural consumer
Answer and working

C. Shorten low-voltage lines by placing small transformers near each few consumers

HVDS takes the medium-voltage line close to loads and uses many small transformers, so LT lines are short — cutting losses, improving voltage and making illegal hooking harder. It does not change consumer voltage, replace MV lines with LT cable, or convert the network to SWER.

Question 9 · easy

A 4-pole alternator in a farm standby generator set must supply 50 Hz. At what speed must the engine drive it?

  1. 1800 rev/min
  2. 1500 rev/min
  3. 3000 rev/min
  4. 750 rev/min
Answer and working

B. 1500 rev/min

N = 120f/P = 120 × 50/4 = 1500 rev/min (check: f = PN/120 = 4 × 1500/120 = 50 Hz). 3000 rev/min is for a 2-pole machine; 750 rev/min for 8 poles; 1800 rev/min gives 60 Hz.

Question 10 · medium

Which device protects a pump motor against running on two lines when one phase of the rural supply fails?

  1. Lightning surge arrester at the pole top
  2. Thirty-milliampere residual current device
  3. High rupturing capacity fuse on each line
  4. Single-phasing preventer or phase-failure relay
Answer and working

D. Single-phasing preventer or phase-failure relay

A phase-failure relay (single-phasing preventer) detects loss or severe imbalance of a phase and trips the contactor; a correctly set overload relay also helps. Surge arresters handle lightning, HRC fuses clear short circuits, and RCDs detect earth leakage — none detects single-phasing reliably.

A study plan for Electrical Machines & Power Utilisation in ICAR AIEEA-PG

This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.

  1. First, the heavy units (50% of the 72 questions): Three-phase induction motors: slip and torque-speed curve (10, 14%); Single-phase motors, including capacitor-start (9, 13%); Wiring and protection: fuses, MCB, ELCB and earthing (9, 13%); DC machines (8, 11%).

    Read the manual chapters for these first and do every worked question you can find on them.

  2. Then the middle band: Motor starters (7, 10%); Rural power distribution and tariffs (7, 10%); Variable-frequency drives (7, 10%); Transformers in practice (6, 8%).

    Aim for one sitting per unit, then mixed questions across them.

  3. Then the lighter units: Power factor correction (5, 7%); Selecting motors for pumps, threshers and processing machines (4, 6%).

    Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.

  4. Leave time for the hard ones: Motor starters (1 hard of 7), DC machines (1 hard of 8), Three-phase induction motors: slip and torque-speed curve (1 hard of 10).

    Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.

  5. Bank the easy marks: Selecting motors for pumps, threshers and processing machines (4 easy of 4); Rural power distribution and tariffs (5 easy of 7).

    Do these early in revision so they are fast on the day.

  6. Finish timed. Sit the subject as a timed set without notes, mark it, and send each wrong answer back to its unit above.

Last updated · How Laisha writes and checks its pages · Report a mistake

Ask Laisha about this

Opens Laisha's chat with your question ready to send. Sign in or start free.

Unlock every question — ICAR AIEEA-PG Electrical Machines & Power Utilisation

US$10 a month · one price worldwide · cancel any time

  • Every practice question in this subject, with full working
  • Timed exam papers and progress by unit
  • Ask Laisha to explain any answer — up to 1,000 questions a month
Free or Smarter
FreeSmarter
Grow guides, pest pages, articlesRead allRead all
Ask Laisha5 a dayUp to 1,000 a month
Exam practiceThe sample on each pageEvery question, timed papers
Crop calendar and pest alerts—For your own fields
Calculators and tools—All
Uploads and reports—100 a month, real files
10 days free for every new account, no card.